CPSC campaign 07507
Hazard
If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube could crack at the threads between the pick-up tube adaptor and the stainless steel tube. If a pick-up tube is cracked, the extinguisher can fail to discharge properly when activated, which can put users at risk during a fire.
Remedy
Pick-up tube replacements will be performed during routine annual maintenance. The pick-up tube assembly is inside the extinguisher and cannot be visually inspected without de-pressurizing and disassembling the extinguisher. This work should only be done by an authorized ANSUL® distributor. Owners concerned about an extinguisher prior to the scheduled maintenance, due to signs of physical damage such as dents or scratches, should contact their authorized ANSUL® distributor to request a free replacement.